3-4.8 GENII PI REM Pulse Input Module
The GENII PI REM Pulse Input Module (Figure 3-12) is powered by 24VAC ±10% @ 50/60 Hz. Power
Consumption is 4 VA maximum.
The GENII PI REM provides 5 opto isolated digital inputs to sense pulsed signals from field equipment.
The voltage detection range is 12 to 24VDC. The GENII PI REM detects pulses with a minimum on time
of 20ms, with a minimum o time of 20ms, which gives a maximum of 25 pulses per second.
R
GENESI S
PULSE INPUT
Remote Expansion Modul e
12
3
AB
C
DE F
G
HI J
RS485 COMMS
CONNECTIONS
END OF
CABLE
JUMPER
POWER
DIGITAL
INPUT
CONNECTIONS
+DI1-
+DI2-
+DI3-
+DI4-
+DI5-
The RS485 Comms connection block is in the upper right section of the module and the End of Cable
Jumper is next to it.
Digital Input terminals are located at the bottom of the module; input signal connections are listed in
Table 3-18.
Figure 3-12:  GENII PI REM Pulse Input Module
Active Reference
Terminal Signal Terminal Signal
A DI 1 + B DI 1 -
C DI 2 + D DI 2 -
E DI 3 + F DI 3 -
G DI 4 + H DI 4 -
I DI 5 + J DI 5 -
Table 3-18:  GENII PI REM Pulse Input Signal Conditions