Genesis II Installation Instructions
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Refer to Table 3-6 below for Analogue Output terminal numbers. There are 16 Analogue active signal
terminals (AO1 through AO16), one for each channel and eight return (Common) terminals. The fewer
number of Common terminals is intended to reduce the overall number of terminals.
Cable screening may be terminated into the Screens Terminals (20 and 21), space permitting.
Alternatively, all cable screens can be combined by soldering within the slotted cable-routing ducts
with a common 1mm
2
earth lead connected to Terminals 20 or 21.
Terminal Signal Terminal Signal
66 AO1 78 AO5
67 AO2 79 AO6
68 AO3 80 AO7
69 AO4 81 AO8
70 Common 82 Common
71 Common 83 Common
72 Common 84 Common
73 Common 85 Common
74 AO9 86 AO13
75 AO10 87 AO14
76 AO11 88 AO15
77 AO12 89 AO16
Table 3-6:  Genesis II DDC Analogue Outputs