3-4.16 GENII MP423 REM Multipoint Module
The Innotech GENII MP423 REM Multipoint Module is a remote expansion device that has both input
and output expansion capabilities. The GENII MP423 REM provides relay outputs for distributed
control, digital inputs for status detection and Thermistor inputs for temperature measurement.
The GENII MP423 REM (Figure 3-20) is powered by 24VAC ±10% @ 50/60 Hz, or powered by 24VDC
±15%. Power Consumption is 4 VA maximum.
Inputs:
10 kΩ thermistor temperature sensor.
4 x 24VAC or DC Isolated switched contact digital inputs.
Outputs:
3 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp
Inductive.
2 x Analogue Output, 0-10V DC ±0.05V into > 2 kΩ load.
The RS485 Comms connection block is in the lower-le section of the module (as illustrated above)
and the End of Cable Jumper is next to it.
The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing
addresses or adding or removing cabling from the terminals.
IMPORTANT
Figure 3-20:  GENII MP423 REM Multipoint Module