Innotech Genesis II Digital Controller (v5) Manuel d'utilisateur Page 70

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 124
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 69
Genesis II Installation Instructions
Page 70 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
3-4.17 GENII MP432 REM Multipoint Module
The Innotech GENII MP432 REM Multipoint Module is a remote expansion device that has both input
and output expansion capabilities. The GENII MP432 REM provides relay outputs for distributed
control, digital inputs for status detection and Thermistor inputs for temperature measurement.
The GENII MP432 REM (Figure 3-21) is powered by 24VAC ±10% @ 50/60Hz, or powered by 24VDC
±15%. Power Consumption is 4 VA maximum.
Inputs:
10kΩ thermistor temperature sensor.
4 x 24VAC or DC Isolated switched contact digital inputs.
Outputs:
2 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp
Inductive.
3 x Analogue Output, 0-10VDC ±0.05V into > 2 kΩ load.
Figure 3-21:  GENII MP432 REM Multipoint Module
The RS485 Comms connection block is in the lower-le section of the module (as illustrated above) and
the End of Cable Jumper is next to it.
The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing
addresses or adding or removing cabling from the terminals.
IMPORTANT